Over-Current Protection

CAUTION!
To reduce the risk of fire, connect the UPS only to a circuit provided with
maximum branch circuit over-current protection as indicated in

Table 7, in accordance with the National Electric Code, NSI/NFPA 70.

ATTENTION !

Pour réduire le risque du feu, reliez l'onduleur seulement à un circuit équipé de
protection maximum de surintensité de circuit de branche comme indiqué au

Table 7, selon le code électrique national, au NSI/NFPA 70.

5.4.1

Ac wiring

Ensure that the lines into and out of the UPS have protective circuit breakers installed in
accordance with the ratings listed in Table 7 for your Power+ model.

The recommended wire size shown in Table 7 is based on a 100 kVA system. The required
circuit breaker sizes in Table 7 are based on the actual maximum power of the system in kVA.

Table 7: Required over-current protection

UPS

POWER CAPACITY

L

INE

F

IELD WIRE SIZE

AS PER

UL

*

R

EQUIRED EXTERNAL

CIRCUIT

-

BREAKER RATING

Ac input

Ac input bypass

10 kVA

Load

35 A

Ac input

Ac input bypass

20 kVA

Load

70 A

Ac input

Ac input bypass

30 kVA

Load

110 A

Ac input

Ac input bypass

40 kVA

Load

500 kcmils,

600 V,

75 °C copper wire

150 A