5.10
First-time Startup
This section describes the procedure for starting up the Power+ for the first time, after having
completed the installation process described in the previous chapter.
1.
Ensure that the maintenance bypass switch is set to NORMAL (OFF), and that no load
devices are connected to the UPS.
Note: When applying power to the POWER+, the system automatically runs the startup process
without a need to press the On/Off button.
2.
Turn the ac input and ac bypass switch ON and wait (for about 2 minutes) for the
POWER+ to initialize.
3.
The start-up sequence will begin and the control panel will show the following
sequence. (The details of the display may vary from what is shown in the illustrations
below, depending on your system's particulars.)
At start-up, the following screen sequence appears:
UPS POWER+
SC25270105
W E L C O M E ! ! !
Figure 34: Start-up screen 1
WARNING !!!
SYSTEM RUNNING IN:
S I L I C O N M O D E (JP2 – IN)
--------PLEASE NOTIFY SUPERVISOR--------
Figure 35: Start-up screen 2
In “SILICON MODE”, commands issued through the Power+ Control Panel are
executed immediately. Operators should exercise caution.
Note: In Figure 35, “Silicon mode” indicates that the configuration jumper is installed, thus
allowing for modifications.
WAIT FOR RESULTS…
STATIC RAM: PASSED R.T CLOCK: PASSED
EEPROM – 1: PASSED
EEPROM – 3: PASSED DC SUPPLIES: PASSED
Figure 36: Start-up screen 3