1 setting ac voltage alarms, Setting ac voltage alarms, Igure – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 101: Etup menu, Larm setup menu, C alarms menu, Et ac alarm voltage levels
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
85
2.
Select Alarm set:
[Main Menu > SETUP > (password) > Ent]
1> Alarm Set 5> Time 9> Silicon
2> Module Conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service 1
Figure 123: Setup menu
8.8.1
Setting Ac Voltage Alarms
1. Select
AC VOLT:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------
Figure 124: Alarm setup menu
2. Select
Set AC High & Low Alarm Levels:
[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT]
1> SET AC HIGH & LOW ALARM LEVELS
2> SET AC ALARMS HYSTERESIS
PLEASE SELECT 1
Figure 125: Ac alarms menu
3.
Use the arrow keys to update values and press Ent:
[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT > Set AC High &
Low Alarm Levels]
AC VOLT SETUP: NOMINAL 110/120 VAC
---- AC ALARM SETUP ----
AC-LOW AC-HIGH
090V 138V
Figure 126: Set ac alarm voltage levels