4 “self-test” option, Self-test” option, Igure – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 90: Enu option, Esult screen from self, Test
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
74
8.4
“Self-test” Option
You can run a self-test at any time without interfering in the normal operation of the POWER+. A
self-test is also initiated by the POWER+ itself each day at midnight.
Figure 104: Main Menu option 3 (“Self Test”)
The failure of a self-test sets on the self-test alarm. The self-test alarm can only be cleared by a
subsequent successful self test, or it can be cleared manually by a maintenance technician.
Powering the POWER+ down and up, for example, does not clear the self-test alarm. This is
because the failure of a self-test is considered a serious event that should not be “forgotten”. A
self-test failure is also recorded in the alarm log.
[Main Menu > SELFTEST]
Wait for results…
STATIC RAM: PASSED R.T CLOCK: PASSED
EEPROM – 1: PASSED
EEPROM – 3: PASSED DC SUPPLIES: PASSED
Figure 105: Result screen from self-test