Able, Attery lifetime vs environmental temperature – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 25
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
9
Free air circulation around the batteries is extremely important for proper battery safety. If
the Power+ is installed in a cabinet, the cabinet must have sufficient ventilation openings
to permit free air circulation around the batteries.
This means that solid glass or acrylic-type door panels are not suitable for a cabinet
housing the Power+, neither for the front cabinet door nor for the rear door.
If the UPS is delivered without batteries, Gamatronic is not responsible for any damage or
malfunction due to incorrect wiring of the batteries.
Protect the batteries from moisture, dampness, and foreign substances.
The temperature of the battery's surroundings influences the batteries' useful lifetime.
Table 1: Battery lifetime vs environmental temperature
E
NVIRONMENTAL
TEMPERATURE
A
CHIEVABLE PERCENTAGE OF
BATTERY
'
S RATED LIFETIME
68 °F (20 °C)
100 %
86 °F (30 °C)
50 %
104 °F (40 °C)
20 %
Please refer to the battery manufacturer’s data sheets for additional information.
When replacing internal batteries, replace with the same number and type!
B
ATTERY
M
ANUFACTURER
P
ART
N
UMBER
HR 1290W
B
ATTERY DESCRIPTION
CSB Battery Co.,
a.k.a CSB Battery Technologies
a.k.a CSB Battery Europe
12 V, 90 W, 22.5 Ah,
valve-regulated lead-acid