1 setting the floating charge, Setting the floating charge, Igure – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 127: Etup menu, Harge setup menu, Et floating charge
![background image](/manuals/337597/127/background.png)
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
111
8.11.1
Setting the Floating Charge
1. Select
Charge:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service
Figure 207: Setup menu
2. Select
Floating parameters setup.:
[Main Menu > SETUP > (password) > Charge]
1> -----
2> Floating parameters setup.
3> ----- (Eq:off)
4> ----- 1
Figure 208: Charge setup menu
3.
Using the arrow keys, set the floating charge, press Ent, and then press Esc:
[Main Menu > SETUP > (password) > Charge > Floating parameters setup.]
Floating charge setup
Voltage setting: 432.0V
Figure 209: Set floating charge