MaxPower Corp 90880 Series Wall Mount User Manual
Ups peripherals, Multiple system configurations, 30 inch wide wall mount design
949 North Larch Avenue Tel (630) 617-9022
Elmhurst, IL 60126
Fax (630) 617-9023
www.ccpower.com
_____________________________________________________________________________________________________
Multiple system configurations
Three breaker design (15A-225A)
30 inch wide wall mount design
Compact design minimizes footprint
Available in 14K to 65K AIC ratings
Optional solenoid key release for added safety
•
•
•
•
•
•
C&C Power offers Wall Mount Maintenance Bypass Breaker Panels available in multiple
configurations.
The 90880 Series MBBC allows the end user to safely isolate the UPS
from utility power and from the load to perform regular service and maintenance.
Our wall mount bypass panels are available in 14K, 35K, or 65K AIC ratings for 480V
applications, and 18K, 22K, or 65K AIC ratings for 208V applications. An SKRU
(solenoid key release) option is available for added safety.
90880 Series Wall Mount Maintenance Bypass Breaker Panels
UPS Peripherals
715-00105 R1
Part Number Configuration
90880 - C 208 3 65 EC 0150 05 MB
1. Cabinet Type
90880 Series
1
2 3
4
5 6 7 8 9
2. Customer Code
C&C Power specific customer code
3. Input & Output Voltage
208 = 208VAC 3PH/4W
480 = 480VAC 3PH/4W
4. Bypass Configuration Breakers
3 = 3 Breakers
5. AIC Rating
14 = 14K (480V, 15-150A models only)
18 = 18K (208V, 15-100A models only)
22 = 22K (208V, 125-225A models only)
35 = 35K (480V, 175-225A models only)
65 = 65K (available on all voltages)
6. Breaker Type
EC = Eaton/Cutler Hammer Series C
7. Bypass Configuration Breaker Size
0015 = 15 Amps, 0020 = 20 Amps
… through 0225 = 225 Amps
8. Lock Configuration
02 = Configuration #2
05 = Configuration #5
06 = Configuration #6
9. Color Code
MB = Black
QB = Beige