2 power+ shutdown (switching to bypass), 3 power+ total shutdown (no ac output), Power+ shutdown (switching to bypass) – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 75: Power+ total shutdown (no ac output), Igure, Ain screen, Switching to bypass, Ypass indication, Total shutdown
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
59
6.2
POWER+ Shutdown (Switching to Bypass)
1.
Switch the load OFF.
2.
Press twice on the On/Off button.
3.
Wait 2 minutes for the POWER+ to shut down. The control screen will indicate UPS
OK (OFF).
LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)
Figure 70: Main screen – switching to bypass
Note: This does NOT switch the entire POWER+ OFF. Power is still delivered to the load but in
bypass.
Figure 71: Bypass indication
6.3
POWER+ Total Shutdown (No Ac Output)
4.
Switch the load OFF.
5.
Press and hold the On/Off button for 10 seconds.
6.
The control screen will indicate UPS OK (OFF).
LOAD LEVEL ---23:14:40---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW Warning !
Figure 72: Main screen – total shutdown