POWER+ Shutdown (Switching to Bypass)

1.

Switch the load OFF.

2.

Press twice on the On/Off button.

3.

Wait 2 minutes for the POWER+ to shut down. The control screen will indicate UPS
OK (OFF).

LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)

Figure 70: Main screen – switching to bypass

Note: This does NOT switch the entire POWER+ OFF. Power is still delivered to the load but in

bypass.

Figure 71: Bypass indication

6.3

POWER+ Total Shutdown (No Ac Output)

4.

Switch the load OFF.

5.

Press and hold the On/Off button for 10 seconds.

6.

The control screen will indicate UPS OK (OFF).

LOAD LEVEL ---23:14:40---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW Warning !

Figure 72: Main screen – total shutdown