beautypg.com

3 configuring the ups, 1 number of redundant upss, Configuring the ups – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 133: Number of redundant upss, Igure, Ervice menu, Ervice, Onfigure menu, Et number of redundant

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

117

2. Press

▲ slowly to test each relay, and press Esc when finished:

[Main Menu > SETUP > (password) > Ent > Service > DryOut Test]

Relay status:
Press ‘UP’ and repeat for relay test(04)
123456 Contacts 1-6
=ON, =OFF

Figure 223: Set UPSs

8.12.3

Configuring the UPS

1. Select

Configure:

[Main Menu > SETUP > (password) > Ent > Service]

1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter

Figure 224: Service menu

8.12.3.1

Number of Redundant UPSs

1. Select

# OF UPSs (redundancy):

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 225: Service > Configure menu

2.

Use the arrow keys to set the number of redundant UPSs and then press Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (redundancy)]

Set number of UPSs (Redundancy)

01 (04 total)

Figure 226: Set number of redundant UPSs