3 configuring the ups, 1 number of redundant upss, Configuring the ups – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 133: Number of redundant upss, Igure, Ervice menu, Ervice, Onfigure menu, Et number of redundant
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
117
2. Press
▲ slowly to test each relay, and press Esc when finished:
[Main Menu > SETUP > (password) > Ent > Service > DryOut Test]
Relay status:
Press ‘UP’ and repeat for relay test(04)
123456 Contacts 1-6
=ON, =OFF
Figure 223: Set UPSs
8.12.3
Configuring the UPS
1. Select
Configure:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 224: Service menu
8.12.3.1
Number of Redundant UPSs
1. Select
# OF UPSs (redundancy):
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 225: Service > Configure menu
2.
Use the arrow keys to set the number of redundant UPSs and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (redundancy)]
Set number of UPSs (Redundancy)
01 (04 total)
Figure 226: Set number of redundant UPSs