beautypg.com

8 enabling/disabling remote commands, 4 enabling/disabling current sharing, Enabling/disabling remote commands – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 139: Enabling/disabling current sharing, Igure, Ervice, Onfigure menu, Nabling, Disabling remote commands, Ervice menu

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

123

8.12.3.8

Enabling/Disabling Remote Commands

1. Select

REM COMMAND:

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 247: Service > Configure menu

2.

Enable or disable remote commands by using the

▲▼arrow keys and Ent::

[Main Menu > SETUP > (password) > Ent > Service > Configure > REM COMMAND]

--- REMOTE COMMANDS EN / DIS ---
SELECT - 1: Disable (selected)
SELECT - 2: Enable

Figure 248: Enabling/disabling remote commands

8.12.4

Enabling/Disabling Current Sharing

1. Select

En/Dis shar:

[Main Menu > SETUP > (password) > Ent > Service]

1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter

Figure 249: Service menu

2.

Enable or disable current sharing by using the

▲▼arrow keys and Ent::

[Main Menu > SETUP > (password) > Ent > Service > Configure > En/Dis shar]

SELECT 1: RST CURRSHAR DISBLD:(selected)
SELECT 2: RST CURRSHAR ENBLD:

--- CURRENT SHARIN RESET EN / DIS ---

Figure 250: Enabling/disabling current sharing