POWER+ Operation Modes

4.9.1

Normal Operation

During normal operation, the UPS draws power from the ac line, feeds dc to the inverter, which
provides ac to the load.

LOAD LEVEL ---11:20:25---
L1: _____ 030A, 120V BATTERY: 434V
L2: ______ 024A, 120V UPS OK (ON)
L3: _______ 022A, 120V STSW OK (INV)

Figure 13: POWER+ control screen in normal operation

Figure 14: Normal operation indication

4.9.2

Battery Operation

During battery operation the battery supplies dc to the inverter, which then provides ac to the
load.

The red alarm flashes to indicate the abnormal status.

LOAD LEVEL no ac 005m ---11:20:25---
L1: _____ 030A, 120V BATTERY: 432V
L2: ______ 022A, 120V UPS OK (ON)
L3: ____ 034A, 120V STSW OK (INV)

AC failed for the

past 5 minutes

Status
indications

Figure 15: AC power failure