3 setting battery over/under temperature alarms, Setting battery over/under temperature alarms, Igure – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 104: Bat-hi, Larm set menu, Nder temperature menu, Et battery maximum temperature alarm
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
88
7.
Use the arrow keys to set BAT-HI, press Ent, and then Esc:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BAT-HI]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 340.0V
Figure 135: Set BAT-HI
8.8.3
Setting Battery Over/Under Temperature Alarms
1. Select
TEMPERATURE:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------
Figure 136: Alarm set menu
2. Select
OVER TEMPERATURE:
[Main Menu > SETUP > (password) > ALARM SET > Temperature]
1> OVER TEMPERATURE
2> UNDER TEMPERATURE
PLEASE SELECT
Figure 137: Over/Under temperature menu
3.
Use the arrow keys to set the battery maximum temperature alarm value and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > Temperature > OVER TEMPERATURE]
SET OVER TEMPERATURE ALARM VALUE
( 2 – 99) DEGREES
45
Figure 138: Set battery maximum temperature alarm