beautypg.com

GF Signet 8900 Multi-Parameter Controller User Manual

Page 9

background image

9

Signet 8900 Multi-Parameter

8059-4

NC COM NO

RELAY A

NC COM NO

RELAY B

NC COM NO

RELAY C

NC COM NO

RELAY D

DC OUTPUT

+ -

DC INPUT

- +

+

S

3

L

-

+

S

3

L

-

INPUT

PASS-THRU

COM

POWER

Signet 3-8059 Relay Module

Test A

Test B

Test C

Test D

Relay A

Relay B

Relay C

Relay D

LISTED
E171559

®

4.5 8059 External Relay Module, optional; install zero (0) or one (1)

Mfr. Part No.

Description

3-8059-4AC

Four external dry-contact relays w/ power supply

3-8059-4

Four external dry-contact relays

3-8050.396

RC Filter Kit

6205-0002

DIN Rail, 1m

6205-0003

End Clips, DIN Rail

The 8900 will support up to eight (8) relays, though only four actually fi t directly
inside its compact

1

/

4

DIN enclosure. 8059 External Relay Modules of four relays

may be connected to the 8900 via digital (S

3

L) at the I/O Module (this does NOT

consume a sensor input channel).

External relays are completely independent of internal relays, so it is not
necessary for Relays 1 & 2 or 3 & 4 to be installed in order to use the external
relays. In the 8900 menus, external relays will always be identifi ed as Relays A,
B, C and D.

8059 versions with power supply are powered by universal AC line voltage
and may be used to power the 8900 with 24 VDC. Also, digital (S

3

L)

pass-thru

terminals on the 8059 can help to reduce sensor wiring congestion at the 8900.
See the 8059 instruction manual for details.

External Relays mount on DIN rail inside a panel and can be tested remotely
from the 8900, or locally with switches built-in for convenience. They also
include LED relay status indicators, but the status of these and all relays is
available at all times in a single screen in the 8900 View mode.

Any and all relays are freely assignable to any channel. Hysteresis and time
delay are adjustable for each relay.

It is perfectly acceptable to mix and match relay types between internal and
external modules. However, NOTE: The 8900 only allows external relays to be
used in modes Off, Low, Hi, Window, USP and Advanced.

8059 External Relay Modules contain dry-contact relays only. These
electromechanical switches are suitable for many general-purpose applications,
AC or DC, including AC loads up to 250 V.

Switching active loads (most commonly inductive) can cause contact arcing
suffi cient to damage relays. The RC Filter Kit or “snubber” is available as an
accessory to reduce or eliminate these damaging effects.

+

S

3

L

-

+

S

3

L

-

OUTPUT 24VDC

+ -

AC INPUT

INPUT

PASS-THRU

L N

8059-4AC

NC COM NO

RELAY C

NC COM NO

RELAY D

NC COM NO

RELAY A

NC COM NO

RELAY B

COM

POWER

Signet 3-8059 Relay Module

Test A

Test B

Test C

Test D

Relay A

Relay B

Relay C

Relay D

LISTED
E171559

®

100 - 240 V
50/60 Hz, 20 VA

89 mm
(3.5 in.)

57 mm
(2.5 in.)

108 mm
(4.25 in.)

+

S

3

L

-

+

S

3

L

-

OUTPUT 24VDC

+ -

AC INPUT

INPUT

PASS-THRU

L N

NC COM NO

RELAY C

NC COM NO

RELAY D

NC COM NO

RELAY A

NC COM NO

RELAY B

COM

32:(5

Signet 3-8059 Relay Module

Test A

Test B

Test C

Test D

Relay A

Relay B

Relay C

Relay D

LISTED
E171559

®