GF Signet 8450 Pressure Transmitter User Manual
GF Signet Tools
CAUTION!
• Remove power to unit before wiring
input and output connections.
• Follow instructions carefully to avoid
personal injury.
Signet 8450-3 Pressure Transmitter
Contents
1. Installation
2. Specifi cations
3. Electrical Connections
4. Menu Functions
Pres1: 4.5
psi
Pres2: 2.3
psi
ENTER
Signet Pressure
Transmitter
Output -
Output +
System Pwr
Loop -
System Pwr
Loop +
2
1
4
3
Sensr Gnd
(SHIELD)
Sensr IN
(RED)
Sensr V+
(BLACK)
7
6
5
8052
92 mm
(3.6 in.)
97 mm
(3.8 in.)
56 mm
(2.2 in.)
41 mm
(1.6 in.
)
Optional
Rear
Cover
SIDE VIEW
Field Mount
96 mm
(3.8 in.)
96 mm
(3.8 in.)
96 mm
(3.8 in.)
quick-clips
gasket
panel
terminals
mounting
bracket
latch
Panel Mount
SIDE VIEW
FRONT VIEW
Field Mount &
Panel Mount
Panel Mount
Installation Detail
107 mm (4.2 in.)
42 mm
(1.7 in.)
65 mm
(2.5 in.)
1. Installation
ProcessPro transmitters are available in two styles: panel mount and fi eld mount. The panel mount is supplied with the necessary
hardware to install the transmitter. This manual includes complete panel mounting instructions.
Field mounting requires one of two separate mounting kits. The 3-8052 integral kit joins the sensor and instrument together into a
single package. The 3-8050 Universal kit enables the transmitter to be installed virtually anywhere.
Detailed instructions for integral mounting or other fi eld installation options are included with the 3-8052 Integral kit or the 3-8050
Universal kit.
1.1 Panel
Installation
1. The panel mount transmitter is designed for installation using a ¼ DIN Punch. For manual panel cutout, an adhesive template is
provided as an installation guide. Recommended clearance on all sides between instruments is 1 inch.
2. Place gasket on instrument, and install in panel.
3. Slide mounting bracket over back of instrument until quick-clips snap into latches on side of instrument.
4. To remove, secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE.
Press quick-clips outward and remove.
3-8450.090-3 Rev. J 01/13 English
*3-8450.090-3*
English
Open-collector output:
Hi, Lo, Off, Programmable:
• Optically isolated, 50 mA max. sink, 30 VDC max. pull-up
voltage
• Hysteresis:
User
adjustable
Environmental
• Operating temperature: -10 °C to 70 °C (14 °F to 158 °F)
• Storage temperature:
-15 °C to 80 °C (5 °F to 176 °F)
• Relative humidity:
0 to 95%, non-condensing
• Maximum altitude:
2000 m (6562 ft)
• Insulation
category:
II
• Rating:
NEMA 4X/IP65 front
Standards and Approvals
• CE, UL listed
• Immunity: EN50082-2
• Emissions:
EN55011 Class B
• Manufactured under ISO 9001 for Quality, ISO 14001
for Environmental Management and OHSAS 18001 for
Occupational Health and Safety.
Declaration of Conformity according to FCC Part 15
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and,
(2) This device must accept any interference received,
including interference that may cause undesired operation.
China RoHS (Go to www.gfsignet.com for details)
2. Specifi cations
General
Compatibility: Signet 2450 Pressure Sensor
Accuracy: ±1% of full scale
Enclosure:
• Case:
PBT
• Panel case gasket: Neoprene
• Window:
Polyurethane coated polycarbonate
• Keypad:
Sealed 4-key silicone rubber
• Weight:
Approx. 325 g (12 oz.)
Display:
• Alphanumeric
2 x 16 LCD
• Update rate:
1 second
• Contrast:
User selected, 5 levels
Electrical
Power:
12 to 24 VDC ±10%, regulated,
60 mA max current
Sensor Input:
• Range:
0-250 psig, 0-17 bar, 0-1700 kPa
Current output:
• 4 to 20 mA, isolated, fully adjustable and reversible
• Max loop impedance:
50 Ω max. @ 12 V,
325
Ω max. @ 18 V,
600
Ω max. @ 24 V
• Update rate:
100 ms
• Accuracy:
±0.03
mA