Signet 8900 Multi-Parameter

Select the decimal location for the Volume display. Must be consistent with the range:

XXXXX.

XXXX.X

XXX.XX

XX.XXX

X.XXXX

If Custom shape is selected, enter the number of measurement points to be used to

characterize the vessel shape.

Minimum 2 points, maximum 20 points. A larger number of points improves accuracy.

Manual: Enter Level and Volume for each custom point. These points are typically

determined by calculation.

If Vert Cylinder or Horiz Cylinder is selected, enter the diameter of the cylinder.

0.0000 to 99999.

If Horiz Cylinder or Rectangular shape is selected, enter the length of the vessel.

0.0000 to 99999.

If Rectangular shape is selected, enter the width of the vessel.

0.0000 to 99999.

V1 Width:

2.0000 ft >

Dampens display, output and relay response rates for this channel.

Off: Near instantaneous updates

Low: 4 s

Med: 8 s

Hi: 32 s

Automatic: Enter Volume only for each custom point. Use this method if the volume

associated with each level can be easily measured.

9.7 Channel Settings: If Channel Type = Level (continued)

V1 Diameter:

10.000 ft >

V1 Length:

5.0000 ft >

L1 Average:

Med >

V1 Cal Points:

10 >

L1 Measurement:

Manual >

Pt01: -1234.5 ft

V1: +5432.1 gal>

V1 Decimal:

**.*** >