beautypg.com

P1 units: psi, T1 units: c, T1 average: med – GF Signet 8900 Multi-Parameter Controller User Manual

Page 27

background image

27

Signet 8900 Multi-Parameter

Select the unit of measure for this pressure channel :

psi bar kPa

P1 Units:

psi >

Select decimal location for this pressure display:

XXXXX. XXXX.X XXX.XX XX.XXX

T1 Units:

C >

Select the unit of measure for this temperature channel:

°C or °F

9.5 Channel Settings: If Channel Type = Pressure

9.6 Channel Settings: If Channel Type = Temperature

Dampens display, output and relay response rates for this channel.

Off: Near instantaneous updates

Low: 4 s

Med: 8 s

Hi: 32 s

Dampens display, output and relay response rates for this channel.

Off: Near instantaneous updates

Low: 4 second averaging; Med: 8 second averaging; Hi: 32 second averaging.

P1 Average:

Med >

T1 Average:

Med >

If this Channel is PRESSURE and the sensor is 4 to 20 mA, set the minimum and

maximum setpoints.

If this Channel is TEMPERATURE and the sensor is 4 to 20 mA, set the minimum and

maximum setpoints.

4mA Set Point 1:

00.000 psi >

20mA Set Point 1

100.00 psi >

P1 Decimal:

**.*** >

4mA Set Point 1:

00.00 °C >

20mA Set Point 1

100.00 °C >