Proportional Pulse mode varies the frequency of pulses in direct
proportion to minimum and maximum setpoints.

The 8900 does not allow use of this mode for Pressure applications.

Example:

The output will be 0 pulses/min. at process values less than 5.0.

The output will be 50 pulses/min. when the process value is 7.5.

The output will be 100 pulses/min. at process values above 10.

0

20

0

0

80

100

elay Pulse idth

as a of elay period

P M
minimum
range

P M
maximum
range

elay is

always

elay is

always

Process value

Pulse Width Modulation

PWM automatically varies the ratio of ON time to OFF time
proportional to minimum and maximum range settings.

The relay period is the sum of the time a relay is ON and the
time it is OFF.

Relay pulse width is the time the relay is ON.

The 8900 must be programmed with the relay period, and with
the low and high setpoints.

The 8900 does not allow use of this mode for Pressure
applications.

Example:

The pulse width will be 0% of the relay period (relay always OFF)
when the process value is less than the minimum range.

The pulse width will be 100% of the relay period (relay always
ON) when the process value is greater than the maximum range.

The pulse width will be 60% of the relay period when the process
value is at 60% of the span between the minimum and maximum
range.

Volumetric Pulse

A pulse is generated each time a specifi ed volume of fl uid is
registered. For fl ow inputs only.

Totalizer Volume

Relay activates and latches when a specifi ed volume of fl uid
is registered. For fl ow inputs only.

Total Volume mode counts the TOTALIZER Units until the
setpoint volume is reached, then activates the relay until the
resettable totalizer is reset.

If the Resettable Totalizer reading is greater than the
setpoint, the relay will be activated immediately. The relay
will be relaxed when the totalizer is reset to zero.

This mode is useful to trigger a reminder when a process is
due, as for a backwash cycle or fi lter change.

Advanced

Relay is activated when a set of three conditions (a, b and c)
are met. See detailed explanation in Section 11.2.

Relay 1 Operator:

( a &(b | c) ) >