Signet 2000 Micro Flow Sensor

Technical Notes:

• Horizontal surface mount (±30°) recommended for

optimum performance.

• Suitable for clean fl uids only. Suspended solids will cause

mechanical failure.

• 1/4 in. NPT or ISO 7/1 - R1/4 (male) port connections

• NEMA 4X/IP65 splashproof enclosure

2. Recommended Sensor Position

1. Compatible Instrument Wiring

Technical Notes:

Use 2-conductor twisted-pair shielded cable for sensor cable splices up to 300 m (1000 ft) max.

Maintain cable shield through cable splice.

Route sensor cable away from AC power lines.

AUX power required when used with any Signet 8550 Process Pro Flow Transmitter.

Signet 2000

Input

Gnd.

10 k

Ω

+

5 to 24
VDC

-

Black

Shield

Red

Other
Instrument

Black (5 to 24 VDC)

Red (Signal out)

Shield (DC return)

Blk
Power

Red
Freq. input
Shld
Gnd

Other

Instrument

Signet

Instrument

30°

30°

Recommended

mounting angles

Vertical mounting

not recommended

SAFETY INSTRUCTIONS
1. Depressurize and vent system prior to installation/removal.
2. Confi rm chemical compatibility before use.
3. Do not exceed maximum temperature/pressure specifi cations.
4. Wear safety goggles or faceshield during installation/service.
5. Do not alter product construction.