beautypg.com

L1 units: ft > show l1 in %: no – GF Signet 8900 Multi-Parameter Controller User Manual

Page 28

background image

28

Signet 8900 Multi-Parameter

9.7 Channel Settings: If Channel Type = Level

Select the unit of measure for this Level channel:

cm

m

in

ft

Yes: Level measurement will be displayed as a percentage of full scale.

No:

Level measurement will be displayed in unit of measure selected in previous setting.

If level measurement will be displayed as a percentage, set the full scale value (100%) in units

of measure.

Select the decimal location for this Level display.

XXXXX.

XXXX.X XXX.XX

XX.XXX X.XXXX

Enter the distance (in units of measure) from the sensor to the zero reference point.

See Appendix B: Level System Confi guration for additional information.

Select the unit of measure for Volume displays from this level sensor:

cm

3

m

3

in

3

ft

3

gal lit lb kg

Yes: Volumetric measurements will be displayed as a percentage of full scale.

No:

Volumetric measurements will be displayed as units selected in previous setting.

If Volume measurement will be displayed a percentage, set the full scale value (100%) in units

of measure.

If a pressure sensor is used for Level measurement, enter the specifi c gravity of the fl uid.

L1 Units:

ft >

Show L1 in %:

No >

L1

100%=

0.00 ft >

V1 Units:

ft3 >

Note: The following channel settings for Volume may be ignored if not applicable to the application.

If this Channel is LEVEL and the sensor is 4 to 20 mA, set the minimum and maximum

setpoints.

Select the shape of the vessel where the level sensor is located.

Vert Cylinder Horiz Cylinder Rectangular

Custom

4mA Set Point 1:

00.000 ft >

20mA Set Point 1

10.00 ft >

L1 Decimal:

**.*** >

Sensor 1 Offset:

+XXX.XX ft >

Show V1 in %:

No >

V1 100% =:

0.0000 gal >

Spec Gravity L1:

1.0000 >

V1 Shape:

Vert Cylinder >