Signet 8900 Multi-Parameter

9.1 Channel Settings: If Channel Type = Flow:

Set K-Factor (pulses per unit volume) from Flow Sensor manual:

Minimum: 0.0001

Maximum: 99999. (Cannot be zero)

Select decimal resolution for Flow Rate display:

XXXXX.

XXXX.X XXX.XX XX.XXX

X.XXXX

This setting identifi es the Totalizer units. It has no effect on any calculation.

Up to eight (8) alphanumeric characters, upper & lower case, serve as a label only.

Tot~ Factor: Sets the volume of each count of the Totalizer as a multiple of the volume

unit of the K-Factor: If K-Factor = pulses per gallon, and Tot~ Factor is set to 1.000, then

Totalizer counts once per gallon; if Tot~ Factor is set to 10.00, then Totalizer counts once

for every 10 gallons, etc.

Minimum: 0.0001

Maximum: 99999.

(Cannot be zero)

Select decimal resolution for Totalizer displays:

XXXXXXXX. XXXXXXX.X XXXXXX.XX

Lock On: EDIT code required to reset the Resettable totalizer to zero.

Lock Off: No EDIT code required to reset the Resettable totalizer to zero.

Dampens display, output and relay response rates for this channel.

Off: Near instantaneous updates

Low: 4 s

Med: 8 s

Hi: 32 s

Set the units of measure for this fl ow channel.

The last character sets the timebase:

Select S (seconds)

M (minutes)

H (hours)

D (days)

F1 Units:

GPM >

Tot1 Reset:

Lock Off >

F1 Average:

Med >

F1 Decimal:

**.*** >

Tot1 Unit:

Gallons >

Tot1 Factor:

60.000 >

Tot1 Decimal:

******.** >

9. Channel

Settings

The Channel Settungs menu changes according to the channel type. This section shows the settings available for each type of sensor.

If this channel is FLOW and the sensor is 4 to 20 mA, set the minimum and maximum

setpoints.

20mA Set Point 1

55.000 GPM >

4mA Set Point 1:

5.0000 GPM >

F1 K-Factor:

60.000 >