Positioner 1067, 5 maintenance – Burkert Type 1067 User Manual
Page 90

E-38-
POSITIONER 1067
5.1 Fault
messages
Faults during switch on
Message Possible
cause
Remedy
INT.ERROR
Internal fault
Not possible, unit defective
Fault messages during AUTOTUNE function
Message Possible
cause
Remedy
TURN POT
Range of the position transducer exceeded
Remove the positioner from
(only with internal feedback transducer option)
the actuator,and turn
the transducer from 180°. cf fig 2.
ERR 2
Actuator not adjustable
Fit the positioner with
Opening time < 0.5 s
bigger air chambers.
Reduce the air pressure
ERR 3
Actuator volume is too big
use a positioner with valves
(opening time > 30 sec.)
connected in parallel
ERR 4
Miscellaneous failure causes:
- manual operation of valve not
- Check manual actuation
in basic setting
parameters
- no air pressure connected
- Check compressed air supply
- position transducer not connected
- Check the electrical connection
of the transducer;If internal position
control system only.(cf fig. 2)
Check the mechanical coupling
of the position controler;if external
position control system (cf fig. 3)
5 MAINTENANCE
5.2
Spare parts ordering codes
Designation Order
code
Electronic board
553183
Power supply board, if connected to single-acting valve type 27xx
553184
Power supply board, if connected to single-acting valve type Namur
553185
Power supply board, if connected to double-acting valve type Namur
553186
Set of 2 rocker valves, DN0,6
553423
Set of 2 rocker valves, DN0,9
553424
Set of 2 rocker valves, DN1,2
553425