POSITIONER 1067
E-33-
4 OPERATION
X-LIMIT
(factory setting: XMIN = 0%, XMAX = 100%): Stroke limitation.
This additional function enables the (physical) stroke to be limited to a given MIN and MAX percentage
value (Fig. 36). In the AUTOMATIC mode the stroke range of the limited stroke is then set to equal
100%. In the MANUAL mode, on the other hand, the physical stroke is displayed. (It should therefore
be noted that a limited stroke will be displayed differently in the AUTOMATIC and MANUAL modes).
Fig. 36 Stroke limitation
Limited plug
travel (%)
Limited plug
travel (%)
Physical plug
travel (%)
Unlimited plug
travel (%)
Setting range:
XMIN:
0 ... 50 % of the total stroke,
XMAX:
50 ... 100 % of the total stroke.
The minimum distance between XMIN and XMAX is 50%.
X-TIME
(factory setting: OPN FAST, CLS FAST): Setting speed limitation
Options:
OPN FAST
(open fast): Opening of the control valve happens with maximal control speed.
OPN SLOW
(open slow): The maximum setting speed of the control valve is limited during
opening.
CLS FAST
(close fast): Closing of the control valve happens with maximal control speed.
CLS SLOW
(close slow): The maximum setting speed is limited when the control valve is
closing.
PCONTRL
(process control): Process controller configuration
SETPOINT
(factory setting: EXTERNAL): Preset desired value.
INTERN:
Desired value can be input using the arrow keys (see § 4.4.2).
EXTERN:
Desired value is preset via the standard signal input.
PARAM:
Set parameters for process controller (PID controller)
KP:
(Proportional correction value or amplification)
Range of settings: 0...99.99 (factory setting: 1.00)
TN:
(reset time)
Range of settings: 0.5...999.9 (factory setting: 999.9)
Setpoint (mA)