Maintenance,Troubleshooting

14.

MainTenance, TrOuBleshOOTing

The process controller Type 8611 is maintenance-free when operated according to the instructions in this manual.

14.1. Malfunctions

The table below contains the possible error messages with cause and remedial action.

error

display / action

cause

remedial action

ERR1

ERR1 is displayed and red LED is
lit. The process actual value is still
displayed.
Binary output B_O1 is activated.

The control remains active.

The process value displayed
by the monitoring window is
exceeded or not reached rela-
tively to the set-point value
(see menu function

B_O1 /

LIMT / REL, chapter 12.15).

For description see
chapter “12.15.4. Error
messages for B_O1 and
B_O2”

ERR2

ERR2 is displayed and red LED is
lit. The process actual value is still
displayed.
Binary output B_O1 is activated.

The control remains active.

The process value displayed
by the monitoring window is
exceeded or not reached abso-
lutely to the fixed process value
limit
(see menu function B_O1 /
LIMT / ABS, chapter 12.15).

ERR3

ERR3 is displayed and red LED is
lit. The process actual value is still
displayed.
Binary output B_O2 is activated.

The control remains active.

The process value displayed
by the monitoring window is
exceeded or not reached rela-
tively to the set-point value
(see menu function B_O2 /
LIMT / REL, chapter 12.16).

For description see
chapter “12.15.4. Error
messages for B_O1 and
B_O2”

ERR4

ERR4 is displayed and red LED is
lit. The process actual value is still
displayed.
Binary output B_O2 is activated.

The control remains active.

The process value displayed
by the monitoring window is
exceeded or not reached abso-
lutely to the fixed process value
limit
(see menu function B_O2 /
LIMT / ABS, chapter 12.16).

ERR5

Display

ERR5

control is deactivated and valve
closes.

Sensor input signal of
process actual value < 2 mA.

Check sensor or cables.
Acknowledge with ENTER
key.

ERR6

Display

ERR6

control is deactivated and valve
closes.

Set-point value input signal
< 2 mA.

Check sensor or cables.
Acknowledge with ENTER
key.

ERR7

Display

ERR7

control is deactivated and valve
closes.

No temperature sensor (PT100)
connected.

Check Pt 100 resistance
thermometer.
Acknowledge with ENTER
key.

Table 38:

Error messages