Maintenance, troubleshooting, Malfunctions – Burkert Type 8611 User Manual
Page 98
98
Maintenance,Troubleshooting
14.
MainTenance, TrOuBleshOOTing
The process controller Type 8611 is maintenance-free when operated according to the instructions in this manual.
14.1. Malfunctions
The table below contains the possible error messages with cause and remedial action.
error
display / action
cause
remedial action
ERR1
ERR1 is displayed and red LED is
lit. The process actual value is still
displayed.
Binary output B_O1 is activated.
The control remains active.
The process value displayed
by the monitoring window is
exceeded or not reached rela-
tively to the set-point value
(see menu function
B_O1 /
LIMT / REL, chapter 12.15).
For description see
chapter “12.15.4. Error
messages for B_O1 and
B_O2”
ERR2
ERR2 is displayed and red LED is
lit. The process actual value is still
displayed.
Binary output B_O1 is activated.
The control remains active.
The process value displayed
by the monitoring window is
exceeded or not reached abso-
lutely to the fixed process value
limit
(see menu function B_O1 /
LIMT / ABS, chapter 12.15).
ERR3
ERR3 is displayed and red LED is
lit. The process actual value is still
displayed.
Binary output B_O2 is activated.
The control remains active.
The process value displayed
by the monitoring window is
exceeded or not reached rela-
tively to the set-point value
(see menu function B_O2 /
LIMT / REL, chapter 12.16).
For description see
chapter “12.15.4. Error
messages for B_O1 and
B_O2”
ERR4
ERR4 is displayed and red LED is
lit. The process actual value is still
displayed.
Binary output B_O2 is activated.
The control remains active.
The process value displayed
by the monitoring window is
exceeded or not reached abso-
lutely to the fixed process value
limit
(see menu function B_O2 /
LIMT / ABS, chapter 12.16).
ERR5
Display
ERR5
control is deactivated and valve
closes.
Sensor input signal of
process actual value < 2 mA.
Check sensor or cables.
Acknowledge with ENTER
key.
ERR6
Display
ERR6
control is deactivated and valve
closes.
Set-point value input signal
< 2 mA.
Check sensor or cables.
Acknowledge with ENTER
key.
ERR7
Display
ERR7
control is deactivated and valve
closes.
No temperature sensor (PT100)
connected.
Check Pt 100 resistance
thermometer.
Acknowledge with ENTER
key.
Table 38:
Error messages