FunctionsoftheProcessOperatingLevel

11.9.

VALV – Manual opening and closing of the

connected actuating elements

If the

VALV menu option is selected, the controller is stopped and the actuating element remains in the last

position. The manipulated variable can now by increased or lowered relatively to the last position by pressing
the key.

The display in the

VALV menu option depends on the control variable set in the MODE menu:

MODE = SCV, 0 - 10, 4 - 20, 2P - T, 3P - T (Reset time T

n

activated, T

n

> 0)

MODE = PCV, 2P - T, 3P - T (Reset time T

n

deactivated, T

n

= 9999)

Back to operating state
AUTOMATIC

VALV

SET

150

L/H

055

PRZ

MODE = SCV, 0 - 10, 4 - 20, 2P - T, 3P - T (Reset time T

n

activated, T

n

> 0)

In the case of cascaded control, the process value and
the flow-rate are displayed alternately

Actuating of Valve 1 (VLV1) (Increasing of the manipulated

variable, Bargraph length increases from left to right

3) 4)

Actuating of Valve 1 (VLV1) (Decreasing of the manipulated

variable, Bargraph length decreases from right to left

3) 4)

Display manipulated variable (

4 – 20, 0 – 10 or PRZ)

Display process value

When leaving the

VALV menu option, the last selected

manipulated variable is taken over.

Figure 24:

VALV; Manual opening and closing of the actuating element

3)

Changing the manipulated variable

Each time the key is pressed:

MODE = SCV, 2P - T, 3P - T

by 1%

MODE = 4 - 20

by 0.2 mA

MODE = 0 - 10

by 0.1 V

Continuous pressing of the key > 80 ms:

Quick adjustment of the manipulated variable

4)

The manipulated variable can be changed between 0 and 100 %.

Only for MODE = 3p - T the manipulated variable can be changed between -100 % and +100 %.

-100 % = Valve 2 is controlled by 100 % pulse duty factor
+100 % = Valve 1 is controlled by 100 % pulse duty factor