FunctionsoftheConfigurationLevel

12.8.

CALI - calibration of the analog inputs and outputs

NOTe!

impaired function due to incorrect calibration.
The calibration must be done by trained staff only

All analog inputs and outputs were calibrated at the factory prior to delivery of the controller Type 8611.
However, it is possible to recalibrate the analog inputs and outputs for services purposes or for checking the
calibration.

Setting in the menu:

CALI

calibration set-point input

calibration sensor input

calibration analog output

KFAC

00.00

SETA

*

)

00.00

IN A

**

)

000.0

TEMP

100.0

TEMP

00.00

SETV

*

)

00.00

IN V

**

)

SAVE

*

)

The display depends on the
selection of the standard signal in
the

SETP menu

(

4 – 20 or 0 – 10).

**

)

The display depends on the
sensor input selected in the
S_IN menu
(

4 – 20 or 0 –10).

0002

CODE

calibration temperature input

Accept tem-

perature

calibration

***

)

The display depends on the
standard signal selected in the
AOUT menu
(

4 – 20 or 0 –10).

(default 0 °C)

(default 100 °C)

Only for external set-point
value default

(

SETP = EXT)

Only for sensor input

(

MODE = ... NORM)

Only for sensor input

(

MODE = ... PT)

20.00

OUTA

***

)

10.00

OUTV

***

)

Figure 51:

CALI; Calibration of the analog inputs and outputs