See chapter 12.3.4) – Burkert Type 8611 User Manual
Page 55

55
FunctionsoftheConfigurationLevel
Setting the minimum control time in the menu:
Selection of
control variable
Continue with
selection of process value input
see Figure 27
MODE
enter minimum control time for control valves
0001
CODE
PCV
0005
TMN1
0005
TMN2
Figure 36:
PCV; Enter minimum control time for control valves
12.3.4.
4–20 / 0-10 - continuous control with 4 - 20 ma or 0 - 10 V
standard signal
This function can be used for operating control valves (e.g. motor valve, positioner) via the analog output using
the control for 4-20mA or alternatively 0-10V standard signal.
Example of a typical use, the flow-rate control in conjunction with a flow-rate sensor and an electric motor control
valve, see Figure 37.
8611
Controller
Set-point value
M
10
0
Pos
8611
Process value
Manipulated variable 0 - 10 V
Flow-rate fitting
Type S030
Controller setting:
MODE = F, 0-10, FREQ
Figure 37:
Example of a flow-rate control with 0 - 10 V control
Setting the continuous control with standard signal in the menu:
Selection of
control variable
Continue with
selection of process value input
see Figure 27
MODE
0001
CODE
selection of standard signal
4 – 20
0 – 10
Figure 38:
MODE; Setting the standard signal
english
Type 8611