FunctionsoftheConfigurationLevel

12.19.

DSPL - setting the display

In this menu, the following settings for the display can be made:

• Activation of the background lighting

• Define what value or what manipulated variable should be displayed after switching on the voltage.

Setting the display in the menu:

DSPL

FACT

NO

L OFF

YES

L OFF

PVAL

CMD

BOTH

SETP

The background lighting remains switched on continuously.

The background lighting switches on when the button is

pressed and switches off automatically after 60 seconds.

Display process actual value

Display manipulated variable

(only for continuous control (MODE

= SCV, 4 – 20 or 0 – 10)

see chapter 12.3.2)

Display set-point value and process

actual value

Display set-point value

Figure 69:

DSPL; Setting the display

display

description

PVAL

Display process actual value. Depending on the unit selected in the

UNIT menu

(see chapter 12.4) the corresponding process actual value with unit is displayed.
In the case of cascaded control, the temperature and the flow-rate value are displayed alter-
nately. In the case of ratio control, the two flow-rate values are displayed alternately.

CMD

Display manipulated variable. Depending on the actuating element selected in the

MODE

menu (see chapter 12.3) the following is displayed:
PRZV: Display manipulated variable for control of proportional valve in [%]
4 – 20: Display manipulated variable for control of analog actuating element in [mA]
0 – 10: Display manipulated variable for control of analog actuating element in [V]

The

CMD function is not available for selection for the actuating elements PCV, 2P – T and

3P – T.

BOTH

Set-point value

(SETP) and process actual value (PVAL) are shown on one display

SETP

Display set-point value. Depending on the control variable selected in the MODE menu
(see chapter 12.3) the following is displayed:
SET: Display set-point value for process control
RATI: Display set-point value for ratio control

Table 36:

Display DSPL