beautypg.com

Burkert Type 8611 User Manual

Page 24

background image

24

ElectricalInstallation

8.2.

electrical installation of the control cabinet model

WaRNiNg!

risk of injury from incorrect installation!

Incorrect installation can damage or destroy the Type 8611 eCONTROL.

• The electrical installation may be performed by authorized electricians only!

9 10 11 12 13 14 15 16 17 18

Jumper 1

Jumper 2

Terminal block 1

Terminal block 2

Terminal block 3

20

19

21 22 23 24 25 26 27

1 2 3 4 5 6 7 8

Figure 9:

Control cabinet model; connection PCB with spring terminals and jumpers

8.2.1.

Terminal assignment

terminal block 1

terminal configuration

external circuit

1

GND – Electrical power supply

24 V DC

1

2

GND

24 V DC ± 10 %
max. residual ripple 10 %

2

24 V DC power supply

3
(

BO2)

Binary output 2 (

B_O2)

3

(1, 6, 8, 11, or 23

24 V / 0 V (max. 1 A) NC / NO

GND)

4
(

BO1)

Binary output 1 (

B_O1)

4

(1, 6, 8, 11, or 23

24 V / 0 V (max. 1 A) NC / NO

GND)

english

Type 8611