ElectricalInstallation

terminal configuration

external circuit

5
(

BO3)

(+) Aeration valve (

PCV) or

valve 1 (

2P – T or 3P – T)

MODE = PCV

5

6

NC

valve max. 1 A

MODE = 2P – T

or

3P – T

5

6

NC / NO

valve max. 1 A

6

(–) Aeration valve (

PCV) or

valve 1 (

2P – T or 3P – T)

7
(

BO4)

(+) Proportional valve (

SCV),

bleed valve (

PCV) or valve 2

(

3P – T)

MODE = 3P – T

7

8

NC / NO

valve max. 1 A

MODE = PCV

7

8

NO

valve max. 1 A

MODE = SCV

7

8

NC

valve max. 1.5 A

8

(–) Proportional valve (

SCV),

bleed valve (

PCV) or valve 2

(

3P – T)

Table 9:

Configuration of terminal block 1

terminal block 2

terminal configuration

external circuit

9

GND – Analog output

9

GND

10
(

AOUT)

(+) Analog output (process value or

manipulated variable
for valve)

10

4 - 20 mA / 0 - 10 V

11

GND – Sensor, actuating element

11

GND

12

24 V DC sensor supply or actuating
element

12

24 V DC

13

not used

not used

14
(

AIN2)

(+) External set-point value / ratio
4 - 20 mA / 0 - 10 V

14

(21

4 - 20 mA / 0 - 10 V (Source)

A-GND)

15

(+) 5 V DC sensor supply (max. 20 mA)

15

(1, 11, or 23

5 V DC

GND)

16

RS485_COM

16

RS485_COM

17

RS485_A (+)

17

RS485_A

18

RS485_B (–)

18

RS485_B

Table 10:

Configuration of terminal block 2

english