Para - adjusting the controller parameters, See chapter 12.13 – Burkert Type 8611 User Manual

Page 73

background image

73

FunctionsoftheConfigurationLevel

12.13.

PARA - adjusting the controller parameters

In this menu, the following parameters can be set for the eCONTROL Type 8611:

• Proportional coefficient (proportional gain for opening and closing the actuating element)

KP

1

,

KP

2

The influence that the proportional coefficient has with regard to the selected actuating element and how the
proportional gain is calculated are described in the following chapter “12.3.1. RATI - Selection of external
sensors for ratio control”

.

• Controller cycle time

TREG

• Reset time

TN, TN_T

• Dead zone

DEAD, DE_T

• Effective direction between process value and valve position

INV

• Zero point shut-off

ZERO

• Defining the start value

STRT

What controller parameters are displayed for setting in the

PARA menu depends on the actuating element

selected in the

MODE menu. See chapter “12.3. MODE - Selection of control variable, actuating element

and process value input”.