Part 4 - software utilities, Pipe and liquid configuration – Dynasonics TFXP Series Transit Time Ultrasonic Flow Meter User Manual
Page 81

Rev. 5/09
-4.3-
TFXP
The first screen that appears after clicking the Configuration button
is the BASIC tab. See Figure 4.3 on page 4.5.
Basic Tab
General Units allows selection of either English (U.S.) or Metric
units of measure. If measurements of the pipe are to be entered in
inches, select English. If measurements are to be entered in
millimeters, select Metric. If the General Units are altered from
those at instrument startup, then click the Download button in the
lower right-hand portion of the screen and recycle power to the
TFXP.
Transducer Type selects the transducer that will be connected to
the TFX flow meter. Select from DTTN, DTTH, DTTS or DTTC
models. This selection will influence transducer spacing and flow
meter performance. If you are unsure about the type of transducer
to which the TFX will be connected, consult the shipment packing
list or call the Dynasonics factory for assistance. A change of
Transducer Type will cause a System Configuration Error to occur.
This error will clear when the microprocessor is reset or power is
cycled on the flow meter.
Pipe and
Liquid
Configuration
Figure 4.2 — “Data Display” Screen
PART 4 - SOFTWARE UTILITIES