Part 3 - keypad configuration – Dynasonics TFXP Series Transit Time Ultrasonic Flow Meter User Manual
Page 50

Rev. 5/09
-3.12-
TFXP
Table 3.2 — Specific Heat Capacity Values
for Ethylene Glycol/Water
Specific Heat Capacity BTU/lb °F
Temperature
Ethylene Glycol Solution (% by Volume)
°F °C 25 30 40 50 60 65 100
-40 -40 n/a n/a n/a n/a 0.68
0.70 n/a
0 -17.8 n/a n/a 0.83 0.78 0.72 0.70 0.54
40 4.4 0.91 0.89 0.845 0.80 0.75 0.72 0.56
80 26.7 0.92 0.90 0.86 0.82 0.77 0.74 0.59
120 84.9 0.93 0.92 0.88 0.83 0.79 0.77 0.61
160 71.1 0.94 0.93 0.89 0.85 0.81 0.79 0.64
200 93.3 0.95 0.94 0.91 0.87 0.83 0.81 0.66
240
115.6
n/a n/a n/a n/a n/a 0.83
0.69
Table 3.3 — Specific Heat Capacity Values
for Propylene Glycol/Water
Specific Heat Capacity BTU/lb °F
Polypropylene Glycol Solution (% by Volume)
0 10 20 30 40 50 60
1.00 0.98 0.96 0.94 0.90 0.85 0.81
Table 3.4 — Specific Heat Capacity Values
for Other Common Fluids
Fluid
Temperature
°F
Temperature
°C
Specific Heat BTU/lb °F
Alcohol, ethyl
32
0
0.65
Alcohol, methyl
54
12
0.60
Brine 32 0
0.71
Brine 60 15
0.72
Sea Water
63
17
0.94
PART 3 - KEYPAD CONFIGURATION