beautypg.com

Part 3 - keypad configuration – Dynasonics TFXP Series Transit Time Ultrasonic Flow Meter User Manual

Page 50

background image


Rev. 5/09

-3.12-

TFXP

Table 3.2 — Specific Heat Capacity Values

for Ethylene Glycol/Water

Specific Heat Capacity BTU/lb °F

Temperature

Ethylene Glycol Solution (% by Volume)

°F °C 25 30 40 50 60 65 100

-40 -40 n/a n/a n/a n/a 0.68

0.70 n/a

0 -17.8 n/a n/a 0.83 0.78 0.72 0.70 0.54

40 4.4 0.91 0.89 0.845 0.80 0.75 0.72 0.56

80 26.7 0.92 0.90 0.86 0.82 0.77 0.74 0.59

120 84.9 0.93 0.92 0.88 0.83 0.79 0.77 0.61

160 71.1 0.94 0.93 0.89 0.85 0.81 0.79 0.64

200 93.3 0.95 0.94 0.91 0.87 0.83 0.81 0.66

240

115.6

n/a n/a n/a n/a n/a 0.83

0.69

Table 3.3 — Specific Heat Capacity Values

for Propylene Glycol/Water

Specific Heat Capacity BTU/lb °F

Polypropylene Glycol Solution (% by Volume)

0 10 20 30 40 50 60

1.00 0.98 0.96 0.94 0.90 0.85 0.81

Table 3.4 — Specific Heat Capacity Values

for Other Common Fluids

Fluid

Temperature

°F

Temperature

°C

Specific Heat BTU/lb °F

Alcohol, ethyl

32

0

0.65

Alcohol, methyl

54

12

0.60

Brine 32 0

0.71

Brine 60 15

0.72

Sea Water

63

17

0.94

PART 3 - KEYPAD CONFIGURATION