Part 3 - keypad configuration, 20 ma calibration – Dynasonics TFXP Series Transit Time Ultrasonic Flow Meter User Manual

Page 65

background image


Rev. 5/09

-3.27-

TFXP

4-20 mA
Calibration

Example 1: To span the 4-20 mA output from -100 GPM to +100
GPM, with 12 mA being 0 GPM, set the FL 4MA and FL 20MA
inputs as follows:

FL 4MA = -100.0

FL 20MA = 100.0


Example 2: To span the 4-20 mA output from 0 GPM to +100
GPM, with 12 mA being 50 GPM, set the FL 4MA and FL 20MA
inputs as follows:

FL 4MA = 0.0

FL 20MA = 100.0

The 4-20 mA ISO-MOD is factory calibrated and should not require
adjustment unless it is replaced.

The CAL 4MA entry allows fine adjustments to be made to the
“zero” of the 4-20 mA output. To adjust the 4 mA output, an
ammeter or reliable reference connection to the 4-20 mA output
must be present.

Figure 3.10 — Typical Multimeter Connection

PART 3 - KEYPAD CONFIGURATION