Page 65

 
 Rev. 5/09 
-3.27-
TFXP
4-20 mA 
Calibration 
Example 1: To span the 4-20 mA output from -100 GPM to +100 
GPM, with 12 mA being 0 GPM, set the FL 4MA and FL 20MA 
inputs as follows: 
FL 4MA = -100.0
FL 20MA = 100.0
 
Example 2: To span the 4-20 mA output from 0 GPM to +100 
GPM, with 12 mA being 50 GPM, set the FL 4MA and FL 20MA 
inputs as follows: 
FL 4MA = 0.0
FL 20MA = 100.0
The 4-20 mA ISO-MOD is factory calibrated and should not require 
adjustment unless it is replaced. 
 
The CAL 4MA entry allows fine adjustments to be made to the 
“zero” of the 4-20 mA output. To adjust the 4 mA output, an 
ammeter or reliable reference connection to the 4-20 mA output 
must be present. 
Figure 3.10 — Typical Multimeter Connection
PART 3 - KEYPAD CONFIGURATION