Model lsb, 5 lubrication, 6 monitoring – Xylem LSB User Manual
Page 86: 7 shutting down, 8 storage / longer periods of non- operation

Installation, Operation and Maintenance Instruction
Model LSB
LSB 100-english
page 82
Revision 02
Artikel Nr. 771076129
Ausgabe 01/2010
6.4.2 Abrasive Media
On pumping liquids with abrasive components
an increased wear at hydraulic and shaft sealing
must be expected. The intervals of inspection
should be reduced compared to the usual
times.
6.4.3 Permitted number of starts
The permitted number of starts of the pump must not
be exceeded, see diagram 6.
1,0
10,0
100,0
1
10
100
1000
Motor power [kW]
m
ax
. p
er
m
. s
ta
rt
s/
h
diagram 6
With electric motors, the permitted number of starts is
given in the attached motor operating instructions.
If two different figures are given, the lower figure is
valid.
6.5 Lubrication
The pump has no bearings and, therefore there´s no
need for lubrication.
For possibly required lubrication of the motor bearings
refer to the Operation and Maintenance Instructions of
the motor supplier.
6.6 Monitoring
In areas endangered to explosion it is
recommended to monitor the temperature of the
bearings and the vibrations of the pump.
Regular monitoring and maintenance will extend
the life of your pump or pump system.
Check pump for leaks at least once a week.
Check the regulating and monitoring devices of
any sealing or flushing systems once a week to
ensure that they function properly. Outgoing
cooling water should be handwarm.
Pumps which are exposed to corrosive chemicals
or to wear through abrasion must be inspected
periodically for corrosion or wear and tear. The
first inspection should be carried out after six
months. All further inspection intervals should be
determined on the basis of the state of the pump.
6.7 Shutting down
Close the valve in discharge pipe right before
(max. 10 seconds) switching off the motor. This is
not necessary if there is a spring-loaded check
valve.
Switch off motor (make sure it runs down quietly).
Close the valve on suction side.
Close auxiliary circuit.
On danger of freezing empty pump and pipes
completely.
If pump remains under pressure and temperature
when stationary: leave existing sealing and
flushing systems switched on.
The shaft sealing must remain sealed if there is a
risk of air being sucked in (in the event of supply
from vacuum systems or parallel operation with
shared suction pipe).
6.8 Storage / longer periods of non-
operation
6.8.1 Storage of new pumps
If the putting into operation shall happen a longer
period after the delivery, we recommend the following
measures for the storage of the pump:
Store pump at a dry place.
Rotate pump by hand at least once a month.
6.8.2 Measures for longer putting out of operation
Pump remains installed and in ready for operation:
Test runs of 5 min. duration must be made in
regular intervals. The span between the test runs
is depending on the plant. However, it should be
made once a week, at least.
6.8.3 Longer periods of non-operation
Start-up must be handled like initial start-up (see
chapter 6).
a) Filled pumps
Switch stand-by pumps on and immediately off
again once a week. Possibly use as main pump.
If the stand-by pump is under pressure and
temperature: leave all existing sealing and flushing
systems swiched on.
Replace motor bearings after 5 years.
b) Drained pumps
Turn shaft at least 1x week (do not switch on
because of dry running).
Replace motor bearings after 5 years.