3 10-ms on-delay timer (ton[10ms]), 1 ) operation, 2 ) format – Yaskawa MP900 Series Ladder Programming Manual User Manual
Page 76

5.2 Relay Circuit Instructions
5.2.3 10-ms ON-Delay Timer (TON[10ms])
5-7
Instructions
5
5.2.3 10-ms ON-Delay Timer (TON[10ms])
( 1 ) Operation
The timer counts the time whenever the timer bit input is 1 (ON). The bit output is set to 1 (ON) when the count value
equals the set value.
If the bit input changes to 0 (OFF) during counting, the timer will stop counting. If the bit input changes to 1 (ON)
again, the timer starts counting again from the beginning (i.e., from 0). The actual counted time (in units of 10 ms) is
stored in the Count register.
The counting error is 10 ms or less.
( 2 ) Format
∗ C and # registers cannot be used.
Bit input
Count value
Set value
0
Bit output
1 (ON)
0 (OFF)
1 (ON)
0 (OFF)
Timer
Bit input →
The set value and count value are in units of 10 ms.
→ Bit output
Parameter Name
Applicable Data Types
B
W
L
F
A
Index
Constant
Set value (Set)
×
{
×
×
×
×
{
Count value (Count)
×
{
*
×
×
×
×
×
Icon:
Key entry: [ON
Set value
Count value