Yaskawa MP900 Series Ladder Programming Manual User Manual
Page 154

5.5 Program Control Instructions
5.5.5 Direct Output String (OUTS)
5-85
Instructions
5
Parameter Table Configuration
The following table gives details about the parameters in the MP2000-series Controller.
∗ If a channel for which the allocation has been deleted in the AO Module detailed definition is specified for the OUTS
instruction, the applicable channel number is output for the bit. This is because it is not possible to read the data on
channels for which allocations have been deleted.
The relation between bits and channels is shown below.
Bit 0: Channel 1
Bit 1: Channel 2
Bit 2: Channel 3
Bit 3: Channel 4
Address
Data
Type
Symbol
Name
Specification
I/O
0
W
RSSEL
Unit selection 1
Specify the Module to output to.
IN
1
W
MDSEL
Unit selection 2
IN
2
W
STS
Status
Each bit receives the input status for one word.
0: Normal, 1: Error
OUT
3
W
N
Number of words
Specify the number of output words (always 1).
IN
4
W
OD1
Output data 1
Specify the data to output.
OUT
:
:
:
:
:
N + 3
W
ODN
Output data N
OUT
Module Name
Parameter
CPU
(IO)
LIO-01/02
(LIO)
LIO-04/05
(LIO32)
LIO-06
(MIXIO)
DO-01
(DO)
AO-01
(AO)
RSSEL
Specify the rack, slot, and subslot of the target Module.
Hexadecimal notation: zxyy hex
x: Rack number from 1 to 4
yy: Slot number from 0 to 9
z: Subslot number from 1 to maximum value (determined by Module specifications)
MDSEL
0 (Not used.)
0 (Not used.)
Offset: 0 or 1
Offset: 0 or 1
Offset: 0 to 3
Channel num-
ber - 1: 0 to 3
STS
Always 0.
Always 0.
Always 0.
Always 0.
Always 0.
*
N
1
1
1 or 2
– MDSEL
1 or 2
– MDSEL
1 to 4
– MDSEL
1 to 4
– MDSEL