A.1 System Service Registers

A-5

System Registers

AppA

( 4 ) Scan Execution Status and Calendar

( 5 ) System Program Software Numbers and Remaining Program Memory Capacity

Name

Register
Address

Remarks

High-speed Scan Set
Value

SW00004

This is the set value of the high-speed scan (0.1 ms).

High-speed Scan Current
Value

SW00005

This is the current value of the high-speed scan (0.1 ms).

High-speed Scan
Maximum Value

SW00006

This is the maximum value of the high-speed scan (0.1 ms).

High-speed Scan Set
Value 2

SW00007

This is the set value of the high-speed scan (1

μs).

High-speed Scan Current
Value 2

SW00008

This is the current value of the high-speed scan (1

μs).

High-speed Scan
Maximum Value 2

SW00009

This is the maximum value of the high-speed scan (1

μs).

Low-speed Scan Set
Value

SW00010

This is the set value of the low-speed scan (0.1 ms).

Low-speed Scan Current
Value

SW00011

This is the current value of the low-speed scan (0.1 ms)

Low-speed Scan
Maximum Value

SW00012

This is the maximum value of the low-speed scan (0.1 ms)

Reserved for system.

SW00013

Not used.

Current Scan Time

SW00014

This is the current value of the scan that is currently being exe-
cuted (0.1 ms).

Calendar: Year

SW00015

1999: 0099 (BCD) (last two digits only)

Calendar: Month Day

SW00016

December 31: 1231 (BCD)

Calendar: Hours and
Minutes

SW00017

23: 59: 2359 (BCD)

Calendar: Seconds

SW00018

59 s: 59 (BCD)

Calendar: Week

SW00019

0: Sunday, 1: Monday, 2: Tuesday, 3: Wednesday, 4: Thursday,
5: Friday, 6: Saturday

Name

Register Address

Remarks

System Program Software Version

SW00020

S†††† (†††† is replaced with the
BCD value.)

System Number

SW00021 to

SW00025

Not used.

Remaining Program Memory Capacity

SL00026

Bytes

Total Memory Capacity

SL00028

Bytes