A.4 overview of user operation error status, Appa, 1 ) user operation error code -1 – Yaskawa MP900 Series Ladder Programming Manual User Manual
Page 383

A.4 Overview of User Operation Error Status
A-9
System Registers
AppA
A.4
Overview of User Operation Error Status
Details are given in registers SW00080 to SW00089 when a user operation error occurs in a program.
( 1 ) User Operation Error Code -1
Name
Register
Address
Contents
DWG.A
Error Count
SW00080
• Error Count
Gives the number of errors that have occurred.
• Error Code
Refer to ( 1 ) User Operation Error Code -1 or ( 2 ) User Operation Error
Code -2 for information on error codes.
Error Code
SW00081
DWG.I
Error Count
SW00082
Error Code
SW00083
DWG.H
Error Count
SW00084
Error Code
SW00085
DWG.L
Error Count
SW00088
Error Code
SW00089
Bit 15
12
Bit 11
0
Error Code
Index error
Error Code
Error Description
System Default
In
te
ger O
perati
ons
0001 hex
Integer operation underflow
-32,768
0002 hex
Integer operation overflow
32,767
0003 hex
Integer operation division error
The A register stays the same.
0009 hex
Double-length integer operation underflow
-2,147,483,648
000A hex
Double-length integer operation overflow
2,147,483,647
000B hex
Double-length integer operation division error
The A register stays the same.
Rea
l Number O
perat
ion
s
0010 hex
Non-numerical integer storage error
Data is not stored. [00000]
0011 hex
Integer storage underflow
Data is not stored. [-32,768]
0012 hex
Integer storage overflow
Data is not stored. [ + 32,767]
0021 hex
Real number storage underflow
Data is not stored. [-1.0E + 38]
0022 hex
Real number storage overflow
Data is not stored. [1.0E + 38]
0023 hex
Real number operation division by zero error
Data is not stored. [F register stays the same.]
0030 hex
Invalid real number operation (not a number)
Data is not stored.
0031 hex
Real number operation exponent underflow
0.0
0032 hex
Real number operation exponent overflow
Maximum Value
0033 hex
Real number operation division error (0/0)
Operation is not executed.
0034 hex
Real number storage exponent underflow
A value of 0.0 is stored.
0035 hex
Real number operation stack error
–
0040 to 0059 hex
Real number operation error in standard system
function
Operation is aborted and output is set to 0.0.
0040 hex: SQRT
0041 hex: SIN
0042 hex: COS
0043 hex: TAN
0044 hex: ASIN
0045 hex: ACOS
0046 hex: ATAN
0047 hex: EXP
0048 hex: LN
0049 hex: LOG
004A hex: DZA
004B hex: DZB
004C hex: LIM
004D hex: PI
004E hex: PD
004F hex: PID
0050 hex: LAG
0051 hex: LLAG
0052 hex: FGN
0053 hex: IFGN
0054 hex: LAU
0055 hex: SLAU
0056 hex: REM
0057 hex: RCHK
0058 hex: BSRCH
0059 hex: SORT
For an index error, 1000, 2000, or 3000 hex is added.