5.10 System Function Instructions
5.10.7 Receive Message (MSG-RCV)
5-258
[ b ] Inputs
Execute (Receive Execution Command)
The message is received when this command turns ON.
Keep the Execute bit ON until the Complete or Error bit turns ON.
Abort (Receive Abort Command)
This command aborts receiving the message. It takes priority over Execute (Receive Execution Command).
Dev-Typ (Communications Device Type)
Specify the communications device type.
CPU Module = 8, 215IF = 1, 217IF = 5, 218IF = 6, 218IF-02 = 16, and SVB-01 = 11
Pro-Typ (Communications Protocol)
Specify the communications protocol. For no-protocol communications, a response is not sent to the remote station.
MEMOBUS: Set this input to 1.
No-protocol: Set this input to 2.
Cir-No (Circuit Number)
Specify the circuit number.
CPU Module = 1 or 2, 215IF = 1 to 8, 217IF = 1 to 24, 218IF = 1 to 8, and SVB-01 = 1 to 16
Ch-No (Channel Number)
Specify the channel number of the communications section. Do not set the same channel number more than once for
the same circuit.
CPU Module = 1, 215IF = 1 to 13, 217IF = 1, 218IF = 1 to 10, and SVB-01 = 1 to 8
PARAM (First Address of Parameter List)
Set the first address of the parameter list. For details on this parameter, refer to [ a ] Parameter Details earlier in this
section.
[ c ] Outputs
Busy (Processing)
This item indicates that processing is in progress. Keep Execute ON while Busy is ON.
Complete (Processing Completed)
This item turns ON for only one scan when processing is completed normally.
Error
This item turns ON for only one scan when an error occurs.
For the causes of the error, refer to information on PARAM00 and PARAM01 in [ a ] Parameter Details earlier in this
section.