5.10 System Function Instructions
5.10.6 Send Message (MSG-SND)
5-243
Instructions
5
[ a ] Parameter Details
This section describes the parameters in detail. The parameter number corresponds to the word offset from the first
address of the parameter list.
For example, if the first address of the parameter list is MA00100, set the value in MW00110 to set PARAM10.
Processing Result (PARAM00)
This parameter outputs the result of processing to the upper byte. The lower byte is used for system analysis.
• 00 hex: Processing (Busy)
• 10 hex: Processing completed (Complete)
• 8 hex: Error
The following errors can occur.
• 81 hex: Function code error
An attempt was made to send an unused function code. Or an unused function code was received.
• 82 hex: Address setting error
The data address, coil offset, input relay offset, input register offset, or hold register offset is out-
side of the valid range.
• 83 hex: Data size error
The size of the send or receive data was set outside of the valid range.
• 84 hex: Circuit number setting error
The set circuit number is outside of the valid range.
• 85 hex: Channel number setting error
The set channel number is outside of the valid range.
• 86 hex: Station address error
The set station number is outside of the valid range.
• 88 hex: Communications section error
The communications section returned an error response.
• 89 hex: Device selection error
A device that cannot be used was selected.
Parameter No.
IN/OUT
Description
MEMOBUS
No-protocol
PARAM00
OUT
Processing result
Processing result
PARAM01
OUT
Status
Status
PARAM02
IN
Remote station number
Remote station number
PARAM03
SYS
Reserved for system.
Reserved for system.
PARAM04
IN
Function code
–
PARAM05
IN
Data address
Data address
PARAM06
IN
Data size
Data size
PARAM07
IN
Remote CPU number
Remote CPU number
PARAM08
IN
Coil offset
–
PARAM09
IN
Input relay offset
–
PARAM10
IN
Input register offset
–
PARAM11
IN
Hold register offset
Register offset
PARAM12
SYS
Reserved for system.
Reserved for system.
PARAM13
SYS
Reserved for system.
Reserved for system.
PARAM14
SYS
Reserved for system.
Reserved for system.
PARAM15
SYS
Reserved for system.
Reserved for system.
PARAM16
SYS
Reserved for system.
Reserved for system.