beautypg.com

Yaskawa VS-616G5 Modbus Plus Communication Card User Manual

Page 92

background image

Data Registers



A-12

Monitor Registers (Read only) – continued

REGISTER

FUNCTION

BIT

DESCRIPTION

(in hex)

NO.

F105h

Fault Content 2

0

External Fault 3 (EF3)

1

External Fault 4 (EF4)

2

External Fault 5 (EF5)

3

External Fault 6 (EF6)

4

External Fault 7 (EF7)

5

External Fault 8 (EF8)

6

not used

7

Overspeed (oS)

8

Speed Deviation (DEV)

9

PG Open (PGo)

10

Input Phase Loss (PF)

11

Output Phase Loss (LF)

12

DCCT Fault (CF)

13

Operator Disconnected (OPR)

14

EEPROM Write-in Fault (ERR)

15

not used

F106h

Fault Content 3

0

Modbus Communication Error (CE)

1

not used

2

not used

3

not used

4

Control Fault (CF)

5

Zero Servo Fault (SVE)

6-15

not used

F107h

CPF Content 1

0

not used

1

not used

2

CPF02 Fault

3

CPF03 Fault

4

CPF04 Fault

5

CPF05 Fault

6

CPF06 Fault

7-15

not used