beautypg.com

Yaskawa VS-616G5 Modbus Plus Communication Card User Manual

Page 101

background image



Data Registers

A-21

Drive Parameter Registers (Read/Write) – continued

REGISTER PARAMETER

PARAMETER

PARAMETER

LIMITS / DESCRIPTION

INITIAL

(in hex)

FUNCTION

SETTING

VALUE

200h

C1-01

Acceleration Time 1

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

201h

C1-02

Deceleration Time 1

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

202h

C1-03

Acceleration Time 2

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

203h

C1-04

Deceleration Time 2

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

204h

C1-05

Acceleration Time 3

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

205h

C1-06

Deceleration Time 3

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

206h

C1-07

Acceleration Time 4

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

207h

C1-08

Deceleration Time 4

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

208h

C1-09

Fast Stop Deceleration Time

0.00 to 600.00 or 0.0 to 6000.0 seconds (1)

10.0 (1)

209h

C1-10

Accel / Decel Time Setting Unit

0

0.01 seconds

1

1

0.1 seconds

20Ah

C1-11

Accel / Decel Time Switching Freq.

0.0 to 400.0 Hz

0.00

20Bh

C2-01

S-curve Characteristic at Accel Start

0.0 to 2.50 seconds

0.20

20Ch

C2-02

S-curve Characteristic at Accel End

0.0 to 2.50 seconds

0.20

20Dh

C2-03

S-curve Characteristic at Decel Start

0.0 to 2.50 seconds

0.20

20Eh

C2-04

S-curve Characteristic at Decel End

0.0 to 2.50 seconds

0.20

20Fh

C3-01

Slip Compensation Gain

0.0 to 2.5

(2)

210h

C3-02

Slip Compensation Primary Delay

Time

0 to 10000 msec.

(2)

211h

C3-03

Slip Compensation Limit

0 to 250%

200

212h

C3-04

Slip Compensation Selection

0

Disabled

0

during Regeneration

1

Enabled

Notes (for this page only):

(1) Values are dependent upon C1-10 setting.

(2) Initial Setting differs depending on the control method (A1-02).