Mstr transaction #4 – Yaskawa VS-616G5 Modbus Plus Communication Card User Manual
Page 55

Examples 9-11
The Data Block registers must be loaded with the appropriate PLC address before the MSTR
block is executed.
DATA BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40150
Receive Global Data
0001h
0001h = the PLC/host device (source of global
data) address.
MSTR Transaction #4
This MSTR transaction writes the global data to all drives that have enabled global data. The
Control Block registers must be loaded with the following data before the MSTR function is
executed.
CONTROL BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40160
Operation Code
0005h
0005h = Global Write
40161
Network Error Code
0000h
The error code returned by Modbus Plus
communications
40162
Number of Registers
0003h
Write to 3 consecutive registers
40163
Data Register Code
XXXX
This register is not used when writing global data
40164
Routing 1
XXXX
This register is not used when writing global data
40165
Routing 2
XXXX
This register is not used when writing global data
40166
Routing 3
XXXX
This register is not used when writing global data
40167
Routing 4
XXXX
This register is not used when writing global data
40168
Routing 5
XXXX
This register is not used when writing global data
The Data Block registers must be loaded with the appropriate Global RUN/STOP and Frequency
Reference data before the MSTR block is executed.
DATA BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40170
Activation Bit Map
Register
0003h
bit 0/on = Operation Signals activated
bit 1/on = Frequency Reference activated
40171
Operation Signals
0002h
Run Reverse = bit 0/off, bit 1/on = 0002h
40172
Freq. Reference
0D80h
34.56 Hz = 3456 (decimal) = 0D80h