Data Registers



A-20

Drive Parameter Registers (Read/Write) – continued

REGISTER PARAMETER

PARAMETER

PARAMETER

LIMITS / DESCRIPTION

INITIAL

(in hex)

FUNCTION

SETTING

VALUE

18Eh

b3-01

Speed Search Selection

0

Disabled

0

1

Enabled

18Fh

b3-02

Speed Search Current

0 to 200 %

100 %

190h

b3-03

Speed Search Dec Time

0.1 to 10.0

2.0

191h

Reserved

192h

b4-01

Timer Function ON-Delay Time

0.0 to 300.0 seconds

0.0

193h

b4-02

Timer Function OFF-Delay Time

0.0 to 300.0 seconds

0.0

194h

b5-01

PID Control Mode Selection

0

Disabled

1

Enabled (D=Feedback)

0

2

Enabled (D=Feed Forward)

195h

b5-02

PID Proportional Gain

0.00 to 10.00

1.00

196h

b5-03

PID Integral Time

0.0 to 360.0 seconds

1.0

197h

b5-04

PID Integral Limit

0.0 to 100.0%

100.0

198h

b5-05

PID Differential Time

0.00 to 10.00 seconds

0.00

199h

b5-06

PID Output Limit

0.0 to 100.0%

100.0

19Ah

b5-07

PID Offset Adjustment

-100.0 to +100.0%

0.0

19Bh

b5-08

PID Primary Delay

0.00 to 10.00 seconds

0.00

19Ch

b6-01

Dwell Frequency at Start

0.0 to 400.0 Hz

0.0

19Dh

b6-02

Dwell Time at Start

0.0 to 10.0 seconds

0.0

19Eh

b6-03

Dwell Frequency at Stop

0.0 to 400.0 Hz

0.0

19Fh

b6-04

Dwell Time at Stop

0.0 to 10.0 seconds

0.0

1A0h

b7-01

Droop Control Gain

0.0 to 100.0

0.0

1A1h

b7-02

Droop Control Delay Time

0.03 to 2.00 seconds

0.05

1A2h

b8-01

Energy Saving Gain

0 to 100%

80

1A3h

b8-02

Energy Saving Frequency

0.0 to 400.0 Hz

0.0

1A4h

b9-01

Zero-Servo Gain

0 to 100

5

1A5h

b9-02

Zero-Servo Completion Width

0 to 16383

10