Yaskawa VS-616G5 Modbus Plus Communication Card User Manual
Page 100

Data Registers
A-20
Drive Parameter Registers (Read/Write) – continued
REGISTER PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
18Eh
b3-01
Speed Search Selection
0
Disabled
0
1
Enabled
18Fh
b3-02
Speed Search Current
0 to 200 %
100 %
190h
b3-03
Speed Search Dec Time
0.1 to 10.0
2.0
191h
Reserved
192h
b4-01
Timer Function ON-Delay Time
0.0 to 300.0 seconds
0.0
193h
b4-02
Timer Function OFF-Delay Time
0.0 to 300.0 seconds
0.0
194h
b5-01
PID Control Mode Selection
0
Disabled
1
Enabled (D=Feedback)
0
2
Enabled (D=Feed Forward)
195h
b5-02
PID Proportional Gain
0.00 to 10.00
1.00
196h
b5-03
PID Integral Time
0.0 to 360.0 seconds
1.0
197h
b5-04
PID Integral Limit
0.0 to 100.0%
100.0
198h
b5-05
PID Differential Time
0.00 to 10.00 seconds
0.00
199h
b5-06
PID Output Limit
0.0 to 100.0%
100.0
19Ah
b5-07
PID Offset Adjustment
-100.0 to +100.0%
0.0
19Bh
b5-08
PID Primary Delay
0.00 to 10.00 seconds
0.00
19Ch
b6-01
Dwell Frequency at Start
0.0 to 400.0 Hz
0.0
19Dh
b6-02
Dwell Time at Start
0.0 to 10.0 seconds
0.0
19Eh
b6-03
Dwell Frequency at Stop
0.0 to 400.0 Hz
0.0
19Fh
b6-04
Dwell Time at Stop
0.0 to 10.0 seconds
0.0
1A0h
b7-01
Droop Control Gain
0.0 to 100.0
0.0
1A1h
b7-02
Droop Control Delay Time
0.03 to 2.00 seconds
0.05
1A2h
b8-01
Energy Saving Gain
0 to 100%
80
1A3h
b8-02
Energy Saving Frequency
0.0 to 400.0 Hz
0.0
1A4h
b9-01
Zero-Servo Gain
0 to 100
5
1A5h
b9-02
Zero-Servo Completion Width
0 to 16383
10