Mstr error codes – Yaskawa VS-616G5 Modbus Plus Communication Card User Manual
Page 43

Diagnostics and Troubleshooting 8-3
MSTR Error Codes
If an error occurs during an MSTR operation, a hexadecimal error code will be displayed in the
second register of the control block (the top section). The form of the code is Mmss, where:
??
M represents the major code
??
m represents the minor code
??
ss represents a subcode
A list of error codes appears in the following table.
Error Code (Hex)
DEFINITION
1001
User-initiated abort
2001
Invalid operation type
2002
User parameter changed
2003
Invalid length
2004
Invalid offset
2005
Invalid length + offset
2006
Invalid slave device data area
2007
Invalid slave device network area
2008
Invalid slave device network routing
2009
Route equal to your own address
200A
Attempting to obtain more global data words than available
30ss
Modbus slave exception response
ss
DEFINITION
01
Slave device does not support the requested operation
02
Nonexistent slave device registers requested
03
Invalid data value requested
04
Unassigned
05
Slave has accepted long-duration program command
06
Function cannot be performed - a long duration command is in effect
08-FF
Unassigned
4001
Inconsistent Modbus slave response
5001
Inconsistent network response
6mss
Routing failure
m
DEFINITION
0 or 1
Routing register 1 (local network)
2
Routing register 2
3
Routing register 3
4
Routing register 4
5
Routing register 5
ss
DEFINITION
01
No response received
02
Program access denied
03
Node off-line and unable to communicate
04
Exception response received
05
Router node data paths busy
06
Slave device down
07
Bad destination address
08
Invalid node type in routing path
10
Slave has rejected the command
20
Initiated transaction forgotten by slave device
40
Unexpected master output path received
80
Unexpected response received