Diagnostics and Troubleshooting 8-3

MSTR Error Codes


If an error occurs during an MSTR operation, a hexadecimal error code will be displayed in the
second register of the control block (the top section). The form of the code is Mmss, where:

??

M represents the major code

??

m represents the minor code

??

ss represents a subcode


A list of error codes appears in the following table.

Error Code (Hex)

DEFINITION

1001

User-initiated abort

2001

Invalid operation type

2002

User parameter changed

2003

Invalid length

2004

Invalid offset

2005

Invalid length + offset

2006

Invalid slave device data area

2007

Invalid slave device network area

2008

Invalid slave device network routing

2009

Route equal to your own address

200A

Attempting to obtain more global data words than available

30ss

Modbus slave exception response

ss

DEFINITION

01

Slave device does not support the requested operation

02

Nonexistent slave device registers requested

03

Invalid data value requested

04

Unassigned

05

Slave has accepted long-duration program command

06

Function cannot be performed - a long duration command is in effect

08-FF

Unassigned

4001

Inconsistent Modbus slave response

5001

Inconsistent network response

6mss

Routing failure

m

DEFINITION

0 or 1

Routing register 1 (local network)

2

Routing register 2

3

Routing register 3

4

Routing register 4

5

Routing register 5

ss

DEFINITION

01

No response received

02

Program access denied

03

Node off-line and unable to communicate

04

Exception response received

05

Router node data paths busy

06

Slave device down

07

Bad destination address

08

Invalid node type in routing path

10

Slave has rejected the command

20

Initiated transaction forgotten by slave device

40

Unexpected master output path received

80

Unexpected response received