Installation of the MB+ Board 3-7

Modbus Plus Communication Connection



Communication between a VS-616G5 drive and the MB+ network requires a physical connection
from your drive to the MB+ network. Connect your network communication cable into P1 (9-pin
“D” shell) on the MB+ board. Modicon offers cables and connectors for the MB+ network.

Modicon Modbus Plus Wiring:


The recommended cable for MB+ network connections is Belden 9841. This cable consists of:

??

One twisted signal pair: blue/white

??

Drain wire: bare

??

Overall aluminized mylar shield


This cable is available from Modicon as the following part numbers:

??

97-9841-100

MBPlus 100 Foot Reel

??

97-9841-500

MBPlus 500 Foot Reel

??

97-9841-01K

MBPlus 1000 Foot Reel


Two types of connectors are available from Modicon for connecting devices to the network. Each
in-line drop requires an in-line connector. The two drops at the ends of the Modbus Plus network
cable each require a terminating connector. When the terminating connectors are installed on the
two extreme ends of the cable, no other termination is required.

??

AS-MBKT-085

MBPlus In-line Connector (quantity 1)

??

AS-MBKT-185

MBPlus Terminating Connector (quantity 1)

??

AS-MBPL-001

MBPlus Connector Assembly Tool



Route the Modbus Plus cable out of the bottom of the drive enclosure. Select a cable routing
method to protect the cable from physical damage and potential electrical interference sources.

Note: Avoid sources of electrical interference capable of inducing noise into the cable.

If a cable must cross power wiring, it must cross only at a right angle.