beautypg.com

Yaskawa VS-616G5 Modbus Plus Communication Card User Manual

Page 114

background image

Data Registers



A-34

Special Registers (Write only)

REGISTER

FUNCTION

DATA

DESCRIPTION

(in hex)

SET

F200

Global Write Enable

Global Write Source Address (0=disabled)

F201

Global Frequency Reference Multiplier

Multiplies global freq. reference before being written to drive (1000 = 1.000 multiplier)

FFDDh

‘ACCEPT’ Command

0

Writes data into Volatile memory

FFFDh

‘ENTER’ Command

0

Writes data into Non-Volatile memory