Mstr transaction #1 – Yaskawa VS-616G5 Modbus Plus Communication Card User Manual
Page 53

Examples 9-9
00030 00033
00031
 
 
00032
00031
00033
 
 
 
MSTR Transaction #1 
 
This MSTR transaction writes to the F200h register of the drive on node #2. The Control Block 
registers must be loaded with the following data before the MSTR block is executed: 
 
CONTROL BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40100
Operation Code
0001h
0001h = Write to Multiple Registers
40101
Network Error Code
0000h
The error code returned by Modbus Plus 
communications 
40102
Number of Registers
0001h
Write to 1 register
40103
Data Register Code
F200h
Global Write Data Code
40104
Routing 1
0002h
Modbus Plus node address of drive = 0002h
40105
Routing 2
0001h
End of routing path = 0001h (Modbus Plus 
requirement) 
40106
Routing 3
0000h
This routing register is not used, must be set to 0
40107
Routing 4
0000h
This routing register is not used, must be set to 0
40108
Routing 5
0000h
This routing register is not used, must be set to 0
 
The Data Block registers must be loaded with the appropriate PLC address before the MSTR 
block is executed. 
 
DATA BLOCK
Register
Number
Register
Description
Register
Data
Data
Description
40110
Receive Global Data
0001h
0001h = the PLC/host device (source of global 
data) address. 
 
 
40160
 
 40170 
 
 MSTR 
 #0010