Data Registers

A-3

Global Read Registers (read only

)

REGISTER

FUNCTION

BIT

DATA

DESCRIPTION

(in hex)

NO.

SET

001h

Operational Command

0

0

Stop Forward

1

Run Forward

1

0

Stop Reverse

1

Run Reverse

2

Terminal 3 Function

3

Terminal 4 Function

4

Terminal 5 Function

5

Terminal 6 Function

6

Terminal 7 Function

7

Terminal 8 Function

8

1

External Fault

9

1

Fault Reset

F005h

Output Frequency

Output Frequency of drive (in 0.1 Hz) (1)

F006h

Output Current

10V/Drive rated current (2)

F008h

DC Bus Voltage

DC Bus Voltage (in 1 V)

F000h

Drive Status

0

1

Run

1

1

Zero-Speed

2

1

Reverse Run

3

1

Reset Signal Input

4

1

Speed Agree

5

1

Drive Operation Ready

6

1

Minor Fault

7

1

Major Fault

8

1

not used

9

1

During Momentary Power Ride-through

A

1

Local / Remote

B

Terminal 9&10 Output

C

Terminal 25 Output

D

Terminal 26 Output

E

1

Motor Selection

F

1

Zero Servo Completion

(1) Scaling depends on the setting of o1-03
(2) Display unit = 0.01A for models CIMR-G5U20P4 thru 25P5 and 40P4 thru 45P5; display unit = 0.1A for models 27P5 thru 2075 and 47P5 thru 4300.