Yaskawa VS-616G5 Modbus Plus Communication Card User Manual
Page 113

Data Registers
A-33
Drive Parameter Registers (Read/Write) – continued
REGISTER PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
500h
o1-01
Monitor Selection
4 to 25, 28, 32, 33
6
501h
o1-02
Monitor Selection after Power-up
1
Frequency Reference
2
Output Frequency
1
3
Output Current
4
Selected Monitor
502h
o1-03
Digital Operator Display Scaling
0 to 39999
0
503h
o1-04
Digital Operator Display Units
0
Hz
0
1
RPM
504h
o1-05
Parameter / Address Display
0
Parameter Number
0
Selection
1
Modbus Address
505h
o2-01
LOCAL / REMOTE Key
0
Disabled
1
Selection
1
Enabled
506h
o2-02
STOP Key Function during
0
Disabled
1
Remote Run
1
Enabled
507h
o2-03
User Parameter Default Value
0
Disabled
1
Set Default
0
2
Clear all
508h
o2-04
kVA Selection (Drive Model No.)
0 to FFh
(1)
509h
o2-05
Digital Operator
0
Drive accepts freq. after ENTER key
0
“Motor Operated Pot”
1
Drive accepts freq. immediately
50Ah
o2-06
Operation Selection when Digital
0
Disabled (operation continues)
0
Operator is disconnected
1
Enabled (motor coast to stop; fault)
50Bh
o2-07
Elapsed Operating Hour Timer Set
0 to 65535 hours
-
50Ch
o2-08
Elapsed Operating Hour Timer
0
Timer active when power applied to drive
0
Selection
1
Timer active when drive is in run mode
50Dh
o2-09
Initialization Mode Selection
0
Japanese Spec.
1
American Spec.
1
2
European Spec.
Notes (for this page only):
(1) Not initialized. Initial value differs depending on the drive capacity.